ORDINANCE 1488ORDINANCE NO. 1488
AN ORDINANCE ADOPTING BY REFERENCE THE 2013 EDITION OF THE
CALIFORNIA FIRE CODE, CHAPTERS 1, DIVISION 21 3, and 4, AND SECTIONS
503, 510.2 AND 1103.2 OF THE INTERNATIONAL FIRE CODE, 2012 EDITION,
AND AMENDING THESE CODES THROUGH EXPRESS FINDINGS OF LOCAL
NECESSITY.
The Council of the City of El Segundo does ordain as follows:
SECTION 1: FINDINGS. The City Council finds that certain local climatic, geological,
or topographical conditions exist as follows:
A. Climatic - The City experiences periods of extremely high temperatures
accompanied by low humidity and high winds each year. These
conditions could create an environment in which the Fire Department may
be unable to control fires occurring in vegetation as well as structures not
having built in fire protection.
B. Geological - The City is located in a seismically active area. A significant
earthquake could render the Fire Department incapable of providing
adequate fire protection. In that instance, built -in fire protection would be
relied upon for controlling most structural fires.
C. After due consideration, the City Council finds and determines that due to
these local climatic, geological, or topographical conditions that
amendments, additions, and deletions to the California Fire Code, 2007
Edition, are reasonably necessary to provide sufficient and effective levels
of fire safety for the protection of life, health and property. Specifically,
these amendments are made as follows:
CFC § 503 — Provides a means of ensuring that fire department
access to buildings and fire hydrants is provided uniformly in the
City during periods of low humidity and high winds, potential
seismic activity, or in areas of restricted access present in the City.
2. CFC § 505.1, 505.1.1 — Provides a means of ensuring that fire
department access to buildings and fire hydrants is provided
uniformly in the City during periods of low humidity and high winds,
potential seismic activity, or in areas of restricted access present in
the City.
3. CFC § 510.2 and 1103.2 — Provides a means of ensuring that safe
and efficient firefighting operations are conducted in buildings with
limited radio reception during periods of low humidity and high
Page 1 of 25
winds, potential seismic activity, or in areas of restricted access
present in the City.
4. CFC § 605.11.3.2.1 — Provides roof access on residential
structures for firefighter smoke and heat ventilation operations that
will provide adequate protection during periods of low humidity and
high winds, potential seismic activity, or in areas of restricted
access present in the City.
5. CFC § 901.4.7 — 910.1. Provides a means of ensuring that fire
protection systems are installed and maintained in a manner that
will provide adequate protection during periods of low humidity and
high winds, potential seismic activity, or in areas of restricted
access present in the City.
6. CFC 903.3.5.3 — Requires that fire sprinkler systems are designed
to allow for water reduction during periods of low humidity and high
winds, potential seismic activity, or in areas of restricted access
present in the City.
7. CFC § 915.1 — 915.8.2.6. Requires the installation of fire protection
and life safety equipment in new mid -rise buildings /structures that
increase the fire and life safety of the structures /buildings in order
to provide adequate fire protection during periods of low humidity
and high winds, potential seismic activity, or in areas of restricted
access present in the City.
8.. CFC § 1030.9. Requires fire escapes to be kept clear, maintained
and an annual inspection by a certified individual to ensure the fire
escapes are operable due to potential seismic activity.
9. CFC § 5601.2 and 5601.3 Prohibits the general use of fireworks,
including "Safe and Sane" fireworks and authorizes the fire code
official to confiscate fireworks in order to reduce the danger from
fire during periods of low humidity and high winds, potential seismic
activity, or in areas of restricted access present in the City.
10. CFC Appendix B § B105.2. Reduces the available fire flow
reduction to 50 percent to increase site available fire flow to provide
adequate fire protection and life safety during periods of low
humidity and high winds, potential seismic activity, or in areas of
restricted access present in the City.
Page 2 of 25
SECTION 2: Chapter 10 to Title 13 of the El Segundo Municipal Code ( "ESMC ") is
amended in its entirety to read as follows:
"CHAPTER 10
13 -10 -2: FIRE CODE
A. SECTIONS:
13 -10 -1: ADOPTION OF CODES.
13 -10 -2: AMENDMENTS, ADDITIONS, AND DELETIONS.
13 -10 -3: ADDING APPENDIX M TO THE CFC.
13 -10 -4: GEOGRAPHICAL LIMITS.
13 -10 -1: ADOPTION OF CODES.
Pursuant to California Government Code §§ 50022.1 to 50022.8, the City adopts and
incorporates by reference the California Fire Code, 2013 Edition ( "CFC "), including
Appendixes A, B, and C published drafted and published by the International Code
Council, 500 New Jersey Avenue NW, 6t" Floor, Washington DC, 20001 -2070 and the
California Building Standards Commission, 2525, Natoma Park Drive, Ste 130,
Sacramento, California 95833. The City also adopts and incorporates by reference
Chapters 1, Division 2, 3, 4, and Section 503 of the International Fire Code, 2012
Edition, published by the International Code Council, not included in the California
Building Standards Code, as modified and amended by this chapter. Should the
changes set forth below conflict with the provisions of any other locally adopted code,
these changes will prevail. The CFC and the IFC will apply to all occupancies within the
City's jurisdiction. One (1) true copy of each code is on file with the City Clerk and is
available for public inspection as required by law.
13 -10 -2: AMENDMENTS, ADDITIONS, AND DELETIONS.
After due consideration, the City Council has found that as a result of existing local
climatic, geological, or topographical conditions that amendments, additions, and
deletions to the CFC are reasonably necessary to provide sufficient and effective levels
of fire safety for the protection of life, health and property. Therefore, the CFC is
amended, added to, or deleted from, as set forth below:
§ 104.10 Investigations. The Fire Department is authorized to promptly investigate
the cause, origin and circumstances of each and every fire, explosion, unauthorized
release of hazardous materials, or any other hazardous condition within the City. If it
appears to the bureau of investigation that such fire is suspicious in origin, it is
authorized to take immediate charge of all physical evidence relating to the cause of
fire and to pursue investigation to its conclusion.
§ 104.10.1 Assistance from other agencies. The Police Department and other
public agencies are authorized to assist the Fire Department in its investigations
when requested to do so.
Page 3 of 25
§ 104.10.2 Technical assistance. When there is a fire, explosion, hazardous
materials incident or other potential life or serious property threatening situation, the
fire code official can request the owner to or operator to hire a private fire protection
or hazardous materials investigator, acceptable to the fire code official and at the
expense of the owner or operator, to provide a full report of the incident, including,
without limitation, such matters as origin, cause, circumstances or proposed solution
to the problem.
§ 104.11.4 Financial Responsibility. Any person who personally, or through
another, willfully, negligently, or in violation of law, sets a fire, allows a fire to be set,
or allows a fire kindled or attended by him /her to escape from his /her control, allows
any hazardous material to be handled, stored, disposed of, or transported in a
manner not in accordance with this Code, State law or nationally recognized
Standards, allows any hazardous material to escape from his /her control, allows
continuation of a violation of this Code is liable for the expense of fighting the fire or
for the expenses incurred during a hazardous materials incident, and such expense
will be a charge against that person.
§ 105.2 Application for Permit. Applications for permits will be made to the fire
prevention office in such form and detail as prescribed by the fire code official.
Applications for permits must be accompanied by such plans as required by the fire
code official. Any applicable permit fees must be paid at the time of application for
the permit.
§ 105.6.48 Battery systems. To install or operate stationary storage battery
systems having a liquid capacity of more than 50 gallons (189 L) for flooded lead
acid, nickel cadmium (NiCad) and valve - regulated lead acid (VRLA), or 1,000
pounds (454 kg) for lithium -ion, used for facility standby power, emergency power or
uninterruptible power supplies. See Section 608.
§ 105.6.49 Woodworking. To operate a business which conducts woodworking,
or operates as a cabinet shop or other similar purposes.
§ 105.7.13 Rooftop obstructions. A construction permit is required to install or
modify solar photovoltaic power systems, rooftop gardens or landscaped roofs.
§ 106.2.1 Inspection requests. It is the duty of the holder of the permit or their duly
authorized agent to notify the fire code official when work is ready for inspection. It
is the duty of the permit holder to provide access to and means for inspection of
such work that are required by this code. Every request for inspection must be filed
not less than two working days before such inspection is desired. Such request may
be in writing or by telephone.
§ 108.4 Filing fee and application. The City will assess a fee in an amount set by
resolution at the time that an appellant files an appeal of any order, decisions, or
determination made by the fire code official relative to the application and
Page 4 of 25
interpretation of this Code. The fee is refundable should the appellant prevail in a
decision by the Board. The appeal must be taken by filing a written notice of appeal,
in letterform, to the Board of Appeals. The Board's decision constitutes the City's
final decision.
§ 109.4 Violation penalties. Persons who violate a provision of this code or fail to
comply with any of its requirements or who erects, installs, alters, repairs or does
work in violation of the approved construction documents or directive of the fire code
official, or of a permit or certificate used under provisions of this code, is guilty of a
misdemeanor, punishable by a fine of not more than $1,000 dollars or by
imprisonment not exceeding 6 months, or both such fine and imprisonment. Each
day that a violation continues after due notice has been served constitutes a
separate offense.
§ 202 GENERAL DEFINITIONS are amended to add and /or modify the following
definitions to read as follows:
"Administrator" means the City Manager, or designee, of the city of El Segundo.
"Building Access" means an exterior door opening conforming to all of the
following:
Suitable and available for fire department use, opening onto or adjacent to
a public way or a fire department access road as described in Section
902.
2. Located not more than 2 feet (609.6 mm) above adjacent ground level.
3. Leading to a space, room or area having foot traffic communication
capabilities with the remainder of the building.
4. Designed to permit access with the use of keys available in an approved
key lock box.
"Fire Code Official" is the Fire Chief or a duly authorized representative.
"Low -Rise Building" is any building that is less than four stories in height from the
lowest level of fire department access. Measurement will be from the topside of
the highest floor level that can be occupied to the lowest floor level of building
access, as defined in Section 202.
"Mid -Rise Building" is any building having space used for human occupancy four
complete stories or more in height while being 75 feet (22,860 mm) or less in
height and not defined as a high -rise building by Section 202. Measurement will
be from the topside of the highest floor level that can be occupied to the lowest
floor level of- building access, as defined in Section 202.
Page 5 of 25
"Open Burning" is the burning of materials wherein products of combustion are
emitted directly into the ambient air without passing through a stack or chimney
from an enclosed chamber. Open burning does not include road flares, smudge -
pots and similar devices associated with safety or occupational uses typically
considered open flames. For the purpose of this definition, a chamber must be
regarded as enclosed when, during th time combustion occurs, only apertures,
ducts, stacks, flues or chimneys necessary to provide combustion air and permit
the escape of exhaust gas are open.
§ 307.1.1 Prohibited Open Burning. Open flame, open burning, recreational
burning, fires in outdoor fireplaces or portable fireplaces that is offensive or
objectionable because of smoke emissions or when atmospheric conditions or local
circumstances make such fires hazardous is prohibited.
§ 308.1.4 Open -flame cooking devices. is deleted
§ 311.5 Placards. is deleted
§ 405.2 Table 405.2 Footnote `a'
a. The frequency in all school levels are allowed to be modified in accordance
with Section 408.3.2. Secondary level schools need only conduct evacuation
drills twice each school year.
§ 408.1 General. is deleted
§ 408.2 Group A occupancies. is deleted
§ 408.3 Group E occupancies and Group R -2 college and university buildings.
is deleted
§ 408.5 1 occupancies. is deleted
§ 408.6 Group 1 -2 occupancies. is deleted
§ 408.7 Group 1 -3 occupancies. is deleted
§ 408.8 Group R -1 occupancies. is deleted
§ 408.9 Group R -2 occupancies. is deleted
§ 408.10 Group R-4 occupancies. is deleted
§ 408.11 Covered mall buildings. is deleted
§ 503, Fire Apparatus Access Roads is adopted with the following amendments:
Page 6 of 25
§ 503.1.1 Buildings and facilities. Approved fire apparatus access roads must be
provided for every facility, building or portion of a building hereafter constructed or
moved into or within the jurisdiction. The fire apparatus access road must comply
with the requirements of this section and extend to within 150 feet (45,720 mm) of all
portions of the facility and all portions of the exterior walls of the of the first story of
the building as measured by an approved route around the exterior of the building or
facility. The fire code official has the authority to designate fire apparatus access
roads on private property.
Exception: The fire code official is authorized to increase to dimension of 150
feet (45,720 mm) where:
1. The building is equipped throughout with an approved automatic sprinkler
system installed in accordance with Section 903.3.1.1, 903.1.2 or 903.3.1.3.
2. Fire apparatus access roads cannot be installed because of location on
property, topography, waterways, nonnegotiable grades or other similar
conditions, and an approved alternative means of fire protection is provided.
3. There are not more than two Group R -3 or Group U occupancies.
§ 503.2.1 Dimensions. Fire apparatus access roads must have an unobstructed
width of not less than 20 feet (6096 mm) exclusive of shoulders, except for approved
security gates in accordance with Section 503.6, and an unobstructed vertical
clearance of not less than 15 feet (4572 mm).
Exception:
When serving only one Group R, Division 3 or Group U Occupancy the
unobstructed width of the access road may be 12 feet (3658 mm).
§ 503.2.1.1 Access roads with vehicle parking. No access roads can be less than
32 feet (9754 mm) in width if the vehicle parking is permitted on one side of the
access road and not less than 40 feet (12,192 mm) if vehicle parking is permitted on
both sides of the access road. To permit the free passage of vehicles, access roads
designated for vehicle parking on only one side must have signs or markings
prohibiting the parking of vehicles on the traffic flow side of the roadway.
§ 503.2.1.2 Road divider. An access road divider into separate adjacent one -way
traffic lanes by a curbed divider or similar obstacle must not be less than 15 feet
(4572 mm) in unobstructed width on each side of the divider.
§ 503.2.4 Turning radius. The inside turning radius of a fire apparatus access road
must be a minimum of 60 feet, outside and 40 feet, inside.
Page 7 of 25
§ 503.4 Obstruction of fire apparatus access roads. Fire apparatus access roads
cannot be obstructed in any manner, including the parking of vehicles. The
minimum widths and clearances established in Section 503.2.1 must be maintained
at all times. Speed bumps and speed humps must be approved before installation.
§ 505.1 Address numbers. Approved address numbers and letters must be
placed on all new and existing buildings and units in such a location as to be plainly
visible and legible from the street or road fronting such buildings and units.
Numbers and letters must be at least four (4) inches in height for residential, six (6)
inches in height for commercial, and twelve (12) inches in height for industrial
buildings and units and may not be located on doors or other areas that can be
obstructed from view. The numbers and letters will be in a color that contrasts with
their background and must be in the City's approved numbering sequence.
Commercial and industrial buildings and units that are served by an alley must also
have approved address numbers and letters posted in a visible location near the
primary door to the alley.
§ 505.1.1 Directory. For complexes and large buildings, a directory or premises
map with approved addressing must be installed and maintained at a location and in
format as approved by the fire code official.
§ 507.5.1.1 Hydrant for sprinkler systems and standpipe systems.
Buildings equipped with a an automatic sprinkler system or a standpipe system
installed in accordance with Sections 903 or 905 must have a fire hydrant within 80
feet of the fire department connection.
Exception: The distance may be permitted to exceed 80 feet where approved by
the fire code official.
§ 510.2 Emergency responder radio coverage in existing buildings. is adopted
§ 605.11.3.2.1 Residential building smoke and heat ventilation. Panels /modules
installed on the roof of residential buildings must be located only on one side of any
ridge in order to allow for Fire Department smoke and heat ventilation operations.
The opposite ridge must have the panels /modules located no higher than 3 feet
below the ridge.
Exceptions:
1. Where the solar panels /modules are spaced a minimum 5 feet from the ridge.
2. Where the building is protected throughout by a fire sprinkler system installed
in accordance with the applicable NFPA Standard.
3. Where the building is provided with approved skylights and /or smoke and
heat vents located in approved locations per the El Segundo Fire Department.
§ 805 Upholstered Furniture and Mattress In New and Existing Buildings. is
deleted
Page 8 of 25
§ 808 Furnishings Other Than Upholstered Furniture and Mattresses or
Decorative Materials in New and Existing Buildings. is deleted
§- 901.4.7 Partial fire sprinkler systems. Where in this Code or the Building Code
a partial fire sprinkler system is required, the fire sprinkler system must be installed,
modified or extended to protect the entire building or structure.
§ 901.11 Problematic systems. In the event of a failure of a fire protection system
or 2 or more alarms in a week where the fire code official finds no evidence of a
situation requiring a response, the fire code official is authorized to require the
building owner or occupant to provide a fire watch until the system is repaired. Fire
watch personnel must be provided with at least one approved means for notification
of the Fire Department and their only duty is to perform constant patrols of the
protected premises and keep watch for fires.
§ 903.2.11.3 Building 4 stories or more in height. An automatic sprinkler system
must be installed throughout all buildings having usable floor area four stories or
more above grade, or buildings attached thereto.
Exceptions:
1. Airport control towers
2. Open parking structures.
3. Occupancies in Group F_2.
§ 903.2.20 Structures in the Smoky Hollow Specific Plan Area. An automatic
sprinkler system must be provided throughout every facility or building hereafter
constructed within the Smoky Hollow Specific Plan Area.
§ 903.3.1.2.2 Protection of attached garages. Residential occupancies protected
by an automatic sprinkler system in accordance with NFPA 13R must have
automatic sprinklers installed in attached garages and in other areas as required by
the fire code official.
§ 903.3.1.3.1 Protection of attached garages. Residential occupancies protected
by an automatic sprinkler system in accordance with NFPA 13D must have
automatic sprinklers installed in attached garages and in other areas as required by
the fire code official.
§ 903.3.5.3 Hydraulically calculated systems. The design of hydraulically
calculated fire sprinkler systems shall not exceed 90% of the water supply capacity.
§ 903.3.8 Shutoff valves. Sprinkler shut off valves are required on each floor of
buildings three stories or greater in height.
§ 905.5.3 Intentionally blank.
Page 9 of 25
§ 907.6.5 Monitoring. All fire alarm and detection systems must be monitored by an
approved central station as defined in NFPA 72. A (UL) Underwriters Laboratories
Certificate or (FM) Factory Mutual Placard must be provided and maintained by a UL
Listed or FM Approved fire alarm contractor who provides runner service in
accordance with the 2013 Edition of NFPA 72, Chapter 26 for all newly installed fire
alarm systems in commercial occupancies. This regulation applies to all fire alarm
systems that are newly installed in commercial occupancies for which permits are
required by the El Segundo Fire Department on or after January 1, 2014. Any
existing fire alarm system in a commercial occupancy wherein the fire alarm control
unit and alarm system components are to be replaced is considered newly installed
for the purposes of this section.
Exception. Supervisory service is not required for:
1. Single and multiple- station smoke alarms required by Section
907.2.11.
2. Smoke detectors in Group 1 -3 occupancies.
3. Automatic sprinkler systems in one and two - family dwellings.
§ 910.1 General. Where required by this Code or otherwise installed, smoke and
heat vents or mechanical smoke exhaust systems and draft curtains must conform
to the requirements of this section.
Exceptions:
1. Frozen food warehouses used solely for storage of Class I and
commodities where protected by an approved automatic sprinkler system.
2. Where areas of buildings are equipped with early suppression fast - response
(ESFR) sprinklers, smoke and heat venting must be provided by mechanical
smoke exhaust systems in accordance with Section 910.4 within these
areas.
SECTION 915 MID -RISE BUILDINGS
SECTION 915.1 General
§ 915.1.1 Scope. In addition to other applicable provisions of this code, other laws
and regulations, and any policies of the fire code official, the provisions of this article
apply to every mid -rise building, of any type construction, newly constructed after the
adoption of this Code, or which undergoes a complete renovation that requires the
complete vacancy of the building.
Exceptions: The following structures, while defined as mid -rise buildings, are
not subject to this article:
Page 10 of 25
1. Buildings used exclusively as open parking garage;
2. Buildings where all floors above the third floor (9,144 mm) level are used
exclusively as open parking garage;
1. Buildings such as power plants, lookout towers, steeples, grain houses,
and similar structures with non - continuous human occupancy, when so
determined by the fire code official;
2. Buildings used exclusively for jails, prisons and hospitals.
§ 915.1.2 Definitions. For definitions of MID -RISE BUILDING and BUILDING
ACCESS, see Section 202.
§ 915.2 Building Access.
§ 915.2.1 Building Access. Building access must be provided and approved by
the fire code official.
§ 915.3 Fire and Life Safety Requirements.
§ 915.3.1 Automatic Fire Sprinklers. Every mid -rise building must be protected
throughout by an automatic fire sprinkler system that is designed and installed in
conformance with NFPA 13. A shut -off valves and a water flow alarm device must be
provided for each floor.
§ 915.3.2 Standpipes. Every mid -rise building must be provided with a class I
standpipe system in each required stairway. The standpipe system must be
interconnected with the fire sprinkler system. The system must consist of 2'/z inch
hose valves provided for each floor level above or below grade. Two hose outlets
must also be located on the roof, outside of each stair shaft enclosure that
penetrates the roof. Hose connections must be located in the exit vestibule, unless
otherwise approved by the fire code official.
§ 915.3.3 Smoke Detection. Smoke detectors must be provided in accordance with
this section. Smoke detectors must be connected to an automatic fire alarm system
installed in accordance with NFPA 72. The actuation of any detector required by this
section will operate the emergency voice alarm signaling system and will place into
operation all equipment necessary to prevent the circulation of smoke through air
return and exhaust ductwork.
§ 915.3.3.1 Location. Smoke detectors must be located as follows:
Page 11 of 25
1. In every elevator machinery room and in all elevator lobbies.
Elevator lobby detectors must be connected to an alarm verification
zone or be listed as a releasing device.
2. In the main return -air and exhaust -air plenum of each air -
conditioning system. Such device must be located in a serviceable
area downstream of the last duct inlet.
3. At each connection to a vertical duct or riser serving two or more
stories from a return -air duct or plenum of an air conditioning
system. In Group R -1 and R -2 Occupancies, an approved smoke
detector may be used in each return -air riser carrying not more than
5,000 cubic feet per minute and serving not more than 10 air inlet
openings.
4. For Group R -1 and R -2 Occupancies, in all corridors serving as a
means of egress for an occupant load for 10 or more.
§ 915.3.4 Smoke Control. A passive or active smoke control system must be
provided for all mid -rise buildings whenever a complete floor is in excess of 55 feet
(16.764 mm) from the lowest point of Fire Department access. Such system must be
mechanical and must be designed, installed and tested to be in compliance with
Section 909.
§ 915.3.5 Fire Alarm System. An approved and listed, automatic and manual, fully
addressable and electronically supervised fire alarm system must be provided in
conformance with this code and any policies of the Fire Prevention Division.
§ 915.3.6 Emergency voice alarm signaling system. The operation of any
automatic or manual fire alarm initiating device must automatically sound an alert
tone followed by a pre- recorded voice instruction giving appropriate information and
direction on a general or selective basis to entire building, occupied and normally
non - occupied areas.
§ 915.3.6.1 Pre - recorded instructions. The content of the voice alarm instruction
must be approved by the El Segundo Fire Department.
§ 915.3.6.2 Manual override. A manual override for emergency voice
communication must be provided for all paging zones.
§ 915.4 Central Control Station.
§ 915.4.1 General. A central control station room for fire department- operations
must be provided. The location and accessibility of the central control station room
must be approved by the fire department. The room must be separated from the
remainder of the building by not less than one -hour, fire resistive occupancy
Page 12 of 25
separation. The room must be a minimum of 96 square feet with a minimum
dimension of 8 feet. It must contain the following as a minimum:
1. The voice alarm and public address panels.
2. The fire alarm annunciator panel.
3. Elevator annunciator panel when the building exceeds 55 feet in
height
4. Status indicators and controls of air handling systems.
5. Controls for unlocking stairwell doors.
6. Annunciator panels for emergency and stand -by power status.
7. Annunciator panels for fire pump status.
8. Complete building plans set.
9. Work table.
10. Elevator control switches for switching of emergency power.
§ 915.4.2 Annunciation identification. Control panels in the central control station
must be permanently identified as to function. Water flow, automatic fire detection
and manually activated fire alarms, supervisory and trouble signals must be
monitored by an approved, UL listed Central Monitoring Station or Proprietary
Monitoring Station and annunciated in the central control station by means of an
audible and visual indicator. For the purposes of annunciation, zoning must be in
accordance with the following:
1. When the system serves more that one building, each building
must be considered separately.
2. Each floor must be considered a separate zone.
3. When one ore more risers serve the same floor, each riser must be
considered a separate zone.
§ 915.5 Elevators.
§ 915.5.1 Standards. Elevators and elevator lobbies must be provided and must
comply with the California Building Code and the following:
§ 915.5.2 General. At least one elevator cab must be assigned for Fire Department
use; which serves all floors of the building. All provisions hereinafter are in
reference to said elevator cab(s).
§ 915.5.2.1 Size. The size of the elevator cab must have dimensions as specified in
Section 915.5.2.1.1.
§ 915.5.2.1.1 Ambulance Stretcher. The elevator cab must be provided with
adequate dimensions to accommodate an ambulance type stretcher in accordance
with the provisions of Section 3002.4a.1 of California Building Code.
§ 915.6 Standby Power.
Page 13 of 25
§ 915.6.1 General. An on -site standby power system conforming to the Electrical
Code must be provided. In the event of failure of the normal power source, the
standby power system must provide an alternate source of electrical power to serve
at least the designated loads as set forth in Section 915.6.2 at full power. The
system may consist of an on -site generator or a system of batteries, or both. The
installation must be in accordance with this code, nationally recognized standards,
and any policies of the fire code official.
§ 915.6.2 Loads. The power load requirements for sizing the standby power system
must include, without limitation to the following:
1. Exit signs and exit path illumination;
2. Fire alarm system;
3. Elevator(s) assigned for fire department use;
4. Electrically driven fire pumps (if provided);
5. Smoke control systems;
6. Stairwell pressurization;
7. Lighting circuits supplying all elevator cabs, elevator lobbies,
generator room, fire pump room, and other areas designated by the
fire code official.
§ 915.6.3 Fuel Supplies. On -site fuel supplies for prime movers of a standby power
generator must be sufficient for at least 48 hours at the generator's listed full load.
Where fuel supplies require automatic transfer into a primary tank from a secondary
fuel storage tank, the fuel transfer system must be provided with redundant fuel
pumps to insure reliability. The fuel supply tank provided must be capable of storing
at least 200% of the calculated amount of fuel needed.
§ 915.7 Emergency Electrical System
§ 915.7.1 General. Electrical systems and equipment specified in Section 915.6 are
classed as emergency systems and must be installed in accordance with this code,
NFPA 110, NFPA 111 and policies of the fire code official. Such systems must
operate within 10 seconds of failure to normal power supply. Such emergency power
supply may be separate from the standby power required for fire pumps and
elevators assigned for fire department use.
§ 915.7.2 Emergency Systems. The following are classed as emergency systems:
1. Exit signs and means of egress illumination
Page 14 of 25
2. Fire alarm system
3. Fire detection system
4. Sprinkler alarm system
5. Elevator cab lighting
6. Smoke control systems.
§ 915.8 Means of Egress
§ 915.8.1 General. Means of egress must comply with the provisions of Section
915.8.
§ 915.8.1 Stairway enclosures. All stairways used for exiting must be protected by
an exit enclosure designed in accordance with the California Building Code, Section
1020.1 and this Section.
§ 915.8.2.1 Construction. Construction of stairway enclosures must in accordance
with the California Building Code, Section 1005.3.3.2.
§ 915.8.2.2 Extent of Enclosure. Stairway enclosures must be continuous and
must fully enclose all portions of the stairway. Exit enclosure must exit directly to the
exterior of the building or include an exit passageway on the ground floor, leading to
the exterior of the building. Each exit enclosure must extend completely through the
roof and be provided with a door that leads onto the roof.
§ 915.8.2.3 Openings and Penetrations. Openings and Penetrations must be as
specified in the California Building Code, Section 1020.1.1.
§ 915.8.2.4 Pressurized Enclosures. A pressurized stairway enclosure must be
provided for all mid -rise buildings whenever a complete floor is in excess of 55 feet
(16.764 mm) from the lowest point of Fire Department access. The pressurized
stairway must be designed and pressurized as specified in the California Building
Code, Section 909.20.
§ 915.8.2.4.1 Vestibules. Pressurized stairway enclosures, serving Mid -Rise
buildings must be provided with a pressurized entrance vestibule on each floor that
complies with the California Building Code, Section 909.20.
§ 915.8.2.4.1.1 Vestibule Size. Vestibule size must be not less than 44 inches in
width and not less than 72 inches in the direction of travel.
§ 915.8.2.4.1.2 Vestibule Construction. Vestibules must have walls, ceilings and
floors of not less than two -hour fire resistive construction.
Page 15 of 25
§ 915.8.2.4.1.3 Vestibule Doors. Vestibule doors must comply with California
Building Code, Section 909.20.
§ 915.8.2.4.1.4 Pressure Differences. The minimum pressure difference within a
vestibule must comply with California Building Code, Section 909.20.
§ 915.8.2.4.1.5 Standpipes. Fire Department standpipe connections and valves
serving the floor must be within the vestibule and located in a manner so as not to
obstruct egress when hose lines are connected and charged.
§ 915.8.2.5 Locking of Stairway doors. All stairway doors that are locked to
prohibit access from the stairway side must have the capability of being unlocked
simultaneously, without unlatching, upon a signal from the fire control room. Upon
failure of normal electrical service, or activation of any fire alarm, the locking
mechanism must automatically retract to the unlocked position. Hardware for locking
of stairway doors must be State Fire Marshal listed and approved by the fire code
official by permit before installation. Stairway doors located between the vestibules
and stairway shaft must not be locked.
§ 915.8.2.6 Communications. A telephone or other two -way communications
system connected to an approved emergency service which operates continuously
must be provided at not less than every third floor in each required exit stairway
vestibule.
§ 1030.10 Fire escape maintenance. Fire escapes must be kept clear and
unobstructed at all times, must be maintained in good working order at all times and
must receive an annual inspection by a Los Angeles Fire Department Regulation 4
certified individual. The inspection records must remain on site for Fire Department
review.
§ 1103.2 Emergency responder radio coverage is existing buildings. is adopted
§ 3304.8 Fire retardant plastic sheeting and tarpaulins. Fire retardant tarpaulins
and sheeting must be used to barricade construction areas from occupied building
spaces and to provide floor or wall protection in occupied buildings.
§ 3206.2 Table 3206.2, Footnote `j' is amended to read as follows:
j. Smoke and heat removal must be accomplished by mechanical ventilation in
accordance with Section 910.4 when storage areas are protected by early
suppression fast response (ESFR) sprinkler systems installed in accordance with
NFPA 13.
§ 5601.2 Fireworks. The manufacturing, possession, storage sale, use and
handling of fireworks, including without limitation, "Safe and Sane" fireworks, is
prohibited
Page 16 of 25
Exceptions:
1. Storage of fireworks in accordance with the requirements for low order
explosives in Title 19, California Code of Regulations, Chapter 10.
2. Storage of fireworks, 1 AG in accordance with the Building Code.
3. Use and handling of fireworks for professional display in accordance with
Title 19, California Code of Regulations, Chapter 6.
§ 5601.3 Seizure of Fireworks. The fire code official has the authority to seize, take
and remove fireworks stored, sold, offered for sale, used or handled in violation of
the provisions of Title 19, California Code of Regulations, Chapter 6 and California
Health and Safety Code, Chapter 9.
Appendix B § B105.2 Buildings other than one- and two- family dwellings. The
minimum fire -flow and flow duration for buildings other than one- and two - family
dwellings is specified in Table B105.1
Exception: A reduction in required fire -flow up to 50 percent, as approved, is
allowed when the building is protected with an approved automatic sprinkler
system installed in accordance with Section 903.1.1 or 903.1.2. The resulting
fire -flow must not be less than 1,500 gallons per minute (5678 Umin) for the
prescribed duration as specified in Table B105.1
13 -10 -3: A new Appendix K Temporary Haunted Houses, Ghost Walks, And Similar
Amusement Uses is added to the CFC to read as follows:
SECTION K101
GENERAL
§ K101.1 Scope. These regulations apply to temporary Haunted Houses, Ghost
Walks, or similar amusement uses, where decorative materials and confusing
sounds and /or visual effects are present.
§ K101.2 Permits. An operational permit is required for Haunted Houses, Ghost
Walks, or similar amusement uses in accordance with Appendix K101.2.
§ K101.2.1 Permit documents. The permit application must include a dimensioned
site plan and floor plan.
A site plan showing the following:
1. The proximity of the event building(s) to other structures or hazardous
areas.
2. The path of travel from the event building or area to the public way.
3. The location of exterior evacuation assembly points.
Page 17 of 25
A floor plan showing the following:
1. Dimensions of the area being used (include total square footage, width, and
types of exits, aisles, or interior exit pathways, etc.).
2. The path of travel must include the layout of any mazes, mirrors or other
display items that may confuse the egress paths.
3. A brief description of what will be depicted in each room or area along the
walk or course including the type of special effects to be utilized.
4. Location of exits, exit signs, and emergency lighting.
5. Location of electrical panel(s) and light switches.
6. Identification of what the normal or prior use of the structure(s) being used is
(e.q., auditorium, school, church)
7. Accessible egress routes.
8. When required, areas of refuge.
9. When required by Section 318.9, fire alarm panel location, manual fire alarm
boxes, and horn /strobe locations.
10. Portable fire extinguisher locations.
11. The location and fuel capacity of all generators.
§ K101.3 El Segundo Department of Planning and Building Safety approval.
Approval to operate a temporary amusement haunted house or similar use or to
change the approved of use of an existing building, or portion thereof, for temporary
amusement haunted house or similar use or to change the approved of use of an
existing building, or portion thereof, for temporary amusement haunted house or
similar use requires approved by the El Segundo Department of Planning and
Building Safety before the Fire Department's final construction document approval
and issuance of an operational permit.
SECTION K102
DEFINITIONS
§ K102.1 [CFC 202] DECORATIVE MATERIALS. All materials applied over the
building interior finish for decorative, acoustical or other effect (such as curtains,
draperies, fabrics, streamers and surface coverings) and all other materials utilized
for decorative effect (such as batting, cloth, cotton, hay, stalks, straw, vines, leaves,
trees, moss and similar items), including foam plastics and materials containing
foam plastics. Decorative materials do not include floor coverings, ordinary window
shades, interior finish and materials 0.025 inch (0.64 mm) or less in thickness
applied directly to and adhering tightly to a substrate.
§ K102.2 HAUNTED HOUSE. A building or structure usually used during the
Halloween season for amusement or entertainment purposes. A Haunted House
may or may not be considered a Special Amusement Building depending on the
layout and effects employed.
§ K102.3 GHOST WALKS. Similar to Haunted Houses and may include both indoor
and outdoor areas where the means of egresses are similarly not readily identifiable.
Page 18 of 25
§ K102.4 [CBC 411.2] SPECIAL AMUSEMENT BUILDING. A special amusement
building is any temporary or permanent building or portion thereof that is occupied
for amusement, entertainment or educational purposes and that contains a device or
system that conveys passengers or provides a walkway along, around or over a
course in any direction so arranged that the means of egress path is not readily
apparent due to visual or audio distractions or is intentionally confounded or is not
readily available because of the nature of the attraction or mode of conveyance
through the building or structure.
SECTION K103
GENERAL REQUIREMENTS
§ K103.1 Allowable structures. Temporary Amusement Haunted Houses, Ghost
Walks, and similar amusement uses which meet the definition of a Special Amusement
Building can only be located in structures that comply with the provisions for Special
Amusement Buildings in accordance with the California Building Code when the planned
layout and effects employed meet the definition of a Special Amusement Building.
§ K103.2 Tents or membrane structures. Tents and membrane structures may
be used when in compliance with all applicable requirements of this Appendix and
when the total floor area of the tent is less than 1,000 square feet and the travel
distance to an exit from any location is less than 50 feet.
§ K103.3 Fire evacuation plans. A fire safety and evacuation plan that complies with
Section 404 of the California Fire Code must be submitted and approved.
§ K103.4 Staffing. The event must be adequately staffed by qualified person(s) to
control the occupant load and assist patrons in exiting should an evacuation become
necessary. Staffing level is determined upon review of plans and may be established at
the discretion of the Fire Code Official.
§ K103.5 Occupant load. Maximum occupant load must conform with Chapter 10
Table 1004.1.1. A sign stating maximum occupancy must be posted in a visible
location near the entrance. The attendant(s) must control the flow of patrons so as
not to exceed this limit.
§ K103.6 Exits. Exiting must be in accordance with Chapter 10 and this Section.
1. Two exits must be provided from each room with an occupant load of 50 or
more. Required exit doors shall swing in the direction of egress.
2. Illuminated exit signs must be provided at each exit serving an occupant load
of 50 or more.
3. Exit doors with a lock or latch are prohibited when serving an occupant load of
50 or more unless it constitutes panic hardware.
Page 19 of 25
4. When tents or membrane structures are approved for use, curtains are not be
allowed to cover the exits.
5. Emergency lighting must be provided in exit pathways.
6. Exhibits and decorative materials cannot obstruct, confuse, or obscure exits,
exit pathways, exit signs, or emergency lights.
7. Additional exit pathway markings, such as low level exit signs and directional
exit path markings may be required.
§ K103.7 Fire protection. Temporary Amusement Haunted Houses, Ghost Walks,
and similar amusement uses which meet the definition of a Special Amusement
Building must be provided with fire protection systems in accordance with Appendix
K103. 7.
Exception: When the total floor area of Haunted Houses or indoor portions of
Ghost Walks are less than 1,000 square feet and the travel distance to an exit is
less than 50 feet.
§ K103.7.1 Fire sprinkler protection. An automatic fire sprinkler system is required
for Haunted Houses and indoor portions of Ghost Walks. Fire sprinkler systems
must comply with Section 903.
§ K103.7.2 Fire detection systems. An approved automatic fire detection system
shall be provided in accordance with Section 907.2.12 as required for special
amusement buildings.
§ K103.7.3 Alarm. Activation of any single smoke detector, the fire sprinkler
system, or other automatic fire detection device shall be in accordance with Section
907.2.12.1.
§ K103.7.4 Emergency voice alarm. Special amusement buildings must provide
an emergency voice /alarm communication system in accordance with Section
907.2.12.3.
§ K103.7.5 Portable fire extinguishers. See Section K103.16.
§ K103.8 Electrical. When required, a permit shall be obtained from the local Building
Official.
§ K103.8.1 Extension cords. Extension cords shall be UL listed and must be
appropriate for the intended use.
§ K103.8.2 Power taps. Only UL listed relocatable power taps with overcurrent
protection may be used when the number of outlets provided is inadequate. Power strips
must be plugged directly into the outlet, and cannot be plugged into one another in
series.
Page 20 of 25
§ K103.8.3 String lighting. Manufacturer's installation instructions must be followed for
the maximum allowable number of string lights that can be connected. When connecting
string lights together, the total amperage of all string lights must be calculated to ensure
they do not exceed the amperage for the extension cord and circuit.
§ K103.8.4 Protection. All extension cords and power strips must be adequately
protected from foot traffic.
§ K103.8.5 Portable generators. When portable generators are utilized, they must be
diesel fuel type and located a minimum of 20 feet away from all structures.
§ K103.8.6 Additional electrical requirements. See California Fire Code Section
605 for additional electrical requirements.
§ K103.9 Decorative materials and interior finishes. Interior wall, ceiling, and
floor finishes must be Class A rated in accordance with the California Building Code.
Also see California Fire Code Chapter 8.
§ K103.9.1 Decorative materials. All decorative materials must be inherently flame
retardant, or be treated with a California State Fire Marshal (SFM) listed flame retardant
material. If the decorative material is treated SFM listed flame retardant material by a
non -SFM licensed applicator, the SFM labeled container and sales receipt must be
provided to the fire code official for inspection purposes. Also see Fire Code Chapter 8.
§ K103.9.2 Flame test. Flame retardant material testing must be completed in
accordance with Section 803.5 of the California Fire Code as referenced from the
California Code of Regulations, Title 19, Division 1, Article 3, Section 3.21(a) and (b).
Proof of testing shall be provided.
§ K103.9.3 Placement of decorative materials. Decorative materials, props and /or
performer platforms cannot obstruct, confuse, or obscure exits, exit signs, exit pathways,
emergency lighting or any component of fire protection systems and equipment (e.g. fire
extinguishers, fire alarm systems, fire sprinklers, etc.) inside or outside the building.
§ K103.10 Smoke generators. The fire code official may restrict use of smoke -
generating equipment if it is determined to be incompatible with smoke alarm(s). Care
and consideration must be used with respect to smoke generator and smoke alarm
locations. Smoke generator and smoke alarm locations shall be approved by the fire
code official.
§ K103.11 Display of motor vehicles. Display of motor vehicles must be in
accordance with Section 2402.18 of the California Fire Code.
§ K103.12 Inspections. A fire and life safety inspection must be conducted by the fire
code official before any haunted house, ghost walk or special amusement building is
made available for public use.
Page 21 of 25
§ K103.13 Signs. "NO SMOKING" signs must be conspicuously posted at the main
entrance and throughout the exhibit.
K103.14 Prohibited areas. Inside storage or use of flammable and /or combustible
liquids, gases, and solids is prohibited. Open flames are prohibited.
§ K103.15 Maintenance. Good housekeeping must be maintained throughout exhibit
and exit pathways, at all times. The means of egress system cannot be obstructed
during event operations.
§ K103.16 Portable fire extinguishers. Fire extinguishers must have a minimum
2A -10B:C rating. Fire extinguishers must be properly mounted and be visible and
accessible at all times. Clearly identify locations with signs or reflective tape. Fire
extinguishers m be located within 50 feet travel distance from anywhere in the
building or structure.
13 -10 -4: GEOGRAPHICAL LIMITS
Geographic limits referred to in certain sections of this Code are established as follows:
Establishment of limits of districts in which storage of flammable or
combustible liquids in outside aboveground tanks is prohibited.
The limits referred to in Sections 5704.2.9.6.1 and 5706.2.4.4 in which the storage
of Class I flammable liquids or Class II combustible liquids in aboveground tanks
outside of buildings is restricted are established as the City of El Segundo's
corporate boundaries.
Exceptions: Such use is allowed in the following zoning districts:
1. The storage of Class I flammable liquids or Class II combustible liquids in
aboveground tanks outside of buildings is allowed in M -1 and M -2, Zones;
2. The storage of Class II combustible liquids in aboveground tanks outside of
buildings is allowed in C -0, MM, MU -N, MU -S or P -F Zones;
Establishment of limits of districts in which storage of liquefied petroleum
gases is to be restricted.
The limits referred to in Section 6104.2 in which storage of liquefied petroleum gas in
excess of an aggregate of 2,000 gallons water capacity is restricted are established
as the City of El Segundo's corporate boundaries.
Exceptions:
1. The storage of liquefied petroleum gas in excess of an aggregate of 2,000
gallons water capacity is allowed in the M -2 Zone, when located at least
one -half (1/2) mile from property zoned or designated for residential use and
Page 22 of 25
at least one -half (1/2) mile from existing residential development with a
density greater than one (1) dwelling unit per acre and at least one -half (1/2)
mile from any hotel or motel.
2. The storage of liquefied petroleum gas in excess of an aggregate of 2,000
gallons water capacity is allowed in M -1 Zone with a Conditional Use Permit
issued by the Planning Department.
SECTION 4: CALIFORNIA ENVIRONMENTAL QUALITY ACT EXEMPTION. The City
Council determines that this ordinance is exempt from review under the California
Environmental Quality Act (California Public Resources Code §§ 21000, et seq.,
"CEQA ") and the regulations promulgated thereunder (14 California Code of
Regulations §§ 15000, et seq., the "CEQA Guidelines ") because it consists only of
minor revisions and clarifications to an existing code of construction - related regulations
and specification of procedures related thereto and will not have the effect of deleting or
substantially changing any regulatory standards or findings required therefor. This
ordinance, therefore, is an action being taken for enhanced protection of the
environment and that does not have the potential to cause significant effects on the
environment. Consequently, it is categorically exempt in accordance with CEQA
Guidelines §§ 15301 as a minor alteration of existing public or private structures
involving no expansion of use; 15305 as a minor alteration in land use limitations which
do not result in any changes in land use or density; and 15308 as an action taken by a
regulatory agency as authorized by California law to assure maintenance or protection
of the environment.
SECTION 5: SAVINGS CLAUSE. Repeal or amendment of any provision of the ESMC
or any other city regulation does will not affect any penalty, forfeiture, or liability incurred
before, or preclude prosecution and imposition of penalties for any violation occurring
before, this Ordinance's effective date. Any such repealed part will remain in full force
and effect for sustaining action or prosecuting violations occurring before the effective
date of this Ordinance.
SECTION 6: SEVERABILITY. If any part of this Ordinance or its application is deemed
invalid by a court of competent jurisdiction, the city council intends that such invalidity
will not affect the effectiveness of the remaining provisions or applications and, to this
end, the provisions of this Ordinance are severable.
SECTION 7: VALIDITY OF PREVIOUS CODE SECTIONS. If this the entire Ordinance
or its application is deemed invalid by a court of competent jurisdiction, any repeal of the
ESMC or other the city ordinance by this Ordinance will be rendered void and cause
such ESMC provision or other the city ordinance to remain in full force and effect for all
purposes.
SECTION 8: The City Clerk is directed to certify the passage and adoption of this
Ordinance; cause it to be entered into the City of El Segundo's book of original
ordinances; make a note of the passage and adoption in the records of this meeting;
Page 23 of 25
and, within fifteen (15) days after the passage and adoption of this Ordinance, cause it
to be published or posted in accordance with California law.
SECTION 9; This Ordinance will become effective on January 1, 2014.
PASSED AND ADOPTED this 5th day of November, 2013.
ill risher, Mayor
Page 24 of 25
ATTEST:
STATE OF CALIFORNIA )
COUNTY OF LOS ANGELES ) SS
CITY OF EL SEGUNDO )
I, Tracy Weaver, City Clerk of the City of El Segundo, California, do hereby certify that
the whole number of members of the City Council of said City is five; that the foregoing
Ordinance No. 1488 was duly introduced by said City Council at a regular meeting held
on the 15th day of October, 2013, and was duly passed and adopted by said City
Council, approved and signed by the Mayor, and attested to by the City Clerk, all at a
regular meeting of said Council held on the 5th day of November, 2013, and the same
was so passed and adopted by the following vote:
AYES: Fisher, Jacobson, Fuentes, Atkinson, Fellhauer
NOES: None
ABSENT: None
ABSTAIN: None
r1
Trady Wea , City Clerk
APPRC
Mark D
By: r.
Karl H. Berger
Assistant Ci A orney
Page 25 of 25