53§ 915.8.2.4.1.4 Pressure Differences. The minimum pressure difference within a vestibule must be in accordance with the California Building Code, Section 909.20. § 915.8.2.4.1.5 Standpipes. Fire Department standpipe connections and valves serving the floor must be within the vestibule and located in a manner so as not to obstruct egress when hose lines are connected and charged. § 915.8.2.5 Locking of Stairway doors. All stairway doors that are locked to prohibit access from the stairway side must have the capability of being unlocked simultaneously, without unlatching, upon a signal from the fire control room. Upon failure of normal electrical service, or activation of any fire alarm, the locking mechanism must automatically retract to the unlocked position. Hardware for locking of stairway doors must be State Fire Marshal listed and approved by the Fire code official by permit before installation. Stairway doors located between the vestibules and stairway shaft must not be locked. § 915.8.2.6 Communications. A telephone or other two -way communications system connected to an approved emergency service which operates continuously must be provided at not less than every third floor in each required exit stairway vestibule. 13 -10-4: GEOGRAPHICAL LIMITS Geographic limits referred to in certain sections of this Code are established as follows: Establishment of limits of districts in which storage of flammable cryogenic fluids in stationary containers are prohibited. The limits referred to in Section 3204.3.1.1 in which storage of flammable cryogenic fluids in stationary containers is prohibited are established as the City of El Segundo's corporate boundaries. Exceptions: Page 19 of 23 u J ,j