Loading...
513. Elevator(s) assigned for fire department use; 4. Electrically driven fire pumps (if provided); 5. Smoke control systems; 6. Stairwell pressurization; 7. Lighting circuits supplying all elevator cabs, elevator lobbies, generator room, fire pump room, and other areas designated by the fire code official. § 915.6.3 Fuel Supplies. On -site fuel supplies for prime movers of a standby power generator must be sufficient for at least 48 hours at the generator's listed full load. Where fuel supplies require automatic transfer into a primary tank from a secondary fuel storage tank, the fuel transfer system must be provided with redundant fuel pumps to insure reliability. The fuel supply tank provided must be capable of storing at least 200% of the calculated amount of fuel needed. § 915.7 Emergency Electrical System § 915.7.1 General. Electrical systems and equipment specified in Section 915.6 are classed as emergency systems and must be installed in accordance with this code, nationally recognized standards, and policies of the fire code official. Such systems must operate within 10 seconds of failure to normal power supply. Such emergency power supply may be separate from the standby power required for fire pumps and elevators assigned for fire department use. § 915.7.2 Emergency Systems. The following are classed as emergency systems: 1. 2. 3. 4. 5. § 915.8 Meat Exit signs and exit path illumination: Fire alarm system: Fire Detection system: Sprinkler alarm system: Elevator cab lighting. is of Egress Page 17 of 23 �:Ji