Loading...
44903.2.10.3 Building 4 stories or more in height. An automatic sprinkler system must be installed throughout all buildings having usable floor area four stories or more above grade, or buildings attached thereto. § 903.2.18 Structures in the Smoky Hollow Specific Plan Area. An automatic sprinkler system must be provided throughout every facility or building hereafter constructed within the Smoky Hollow Specific Plan Area. § 903.3.1.2.2 Protection of attached garages. Residential occupancies protected by an automatic sprinkler system in accordance with NFPA 13R must have automatic sprinklers installed in attached garages and in other areas as required by the fire code official. § 903.3.1.3.1 Protection of attached garages. Residential occupancies protected by an automatic sprinkler system in accordance with NFPA 13D must have automatic sprinklers installed in attached garages and in other areas as required by the fire code official. § 903.3.8 Shutoff valves. Sprinkler shut off valves are required on each floor of buildings two stories or greater in height. § 905.5.3 Intentionally blank. § 910.1 General. Where required by this Code or otherwise installed, smoke and heat vents or mechanical smoke exhaust systems and draft curtains must conform to the requirements of this section. Exceptions: 1. Frozen food warehouses used solely for storage of Class I and II commodities where protected by an approved automatic sprinkler system. 2. Where areas of buildings are equipped with early suppression fast - response (ESFR) sprinklers, smoke and heat venting must be provided by mechanical smoke exhaust systems in accordance with Section 910.4 within these areas. Page 10 of 23 4 ��