39threatening situation, the fire code official can request the owner to or operator to
hire a private fire protection or hazardous materials investigator, acceptable to the
fire code official and at the expense of the owner or operator, to provide a full report
of the incident, including, without limitation, such matters as origin, cause,
circumstances or proposed solution to the problem.
Appendix Chapter 1 § 105.2 Application for Permit. Applications for permits will
be made to the fire prevention office in such form and detail as prescribed by the
GhW fire code official. Applications for permits must be accompanied by such plans
as required by the fire code official. Any applicable permit fees must be paid at the
time of application for the permit.
Appendix Chapter 1 § 105.6.48 Battery systems. To install or operate stationary
storage battery systems having a liquid capacity of more than 50 gallons (189 L) for
flooded lead acid, nickel cadium (NiCad) and valve - regulated lead acid (VRLA), or
1,000 pounds (454 kg) for lithium -ion, used for facility standby power, emergency
power or uninterruptible power supplies. See Section 608.
Appendix Chapter 1 § 105.6.49 Woodworking. To operate a business which
conducts woodworking, or operates as a cabinet shop or other similar purposes.
§ 202 GENERAL DEFINITIONS are amended to add and /or modify the following
definitions to read as follows:
"Administrator" means the City Manager, or designee, of the city of El Segundo.
"Building Access" means an exterior door opening conforming to all of the
following:
1. Suitable and available for fire department use, opening onto or adjacent to a
public way or a fire department access road as described in Section 902.
2. Located not more than 2 feet (609.6 mm) above adjacent ground level.
Page 5 of 23
039